CATEGORIES
Kyoritsu KEW 3132A
Kyoritsu 3132a analogue insulation/continuity tester
|
KYORITSU 3132A ANALOGUE INSULATION/CONTINUITY TESTER
- Dust and drip proof construction. (designed to IEC 60529 IP54)
- Designed to meet IEC 61010-1 and IEC 61557 safety standard.
- 1mA rated test current at the minimum resistance.
- 200mA measuring current on continuity testing.
- Automatic discharge of circuit capacitance. (Any charge stored in the circuit under test will be automatically discharged after testing.)
- Live circuit warning buzzer and neon lamp.
- Small and lightweight. Shock resistant new case material.
- AC voltmeter with linear, easy-to-read scale.
- Operates on AA, R6P×6 dry batteries.
Insulation Resistance
Test Voltage : 250V/500V/1000V
Measuring Ranges (Mid-scale Value) : 100MOhms/200MOhms/400MOhms (1MOhms) (2MOhms) (4MOhms)
Output Voltage on open circuit :
Rated test voltage:+20%, -0%
Nominal Current: 1mA DC min.
Output Short :
Circuit Current : 1~2mA DC
Accuracy : 0.1~10MOhms/0.2~20MOhms/0.4~40MOhms
(Accuracy Guaranteed Ranges) ±5% of indicated value
Continuity
Measuring Ranges (Mid-scale Value) :
3Ohms/500Ohms (1.5Ohms) / (20Ohms)
Output Voltage on open circuit : 4.1V DC approx.
Measuring Current : 210mA DC min.
Accuracy : ±1.5% of scale length
AC Voltage
AC Voltage : 0~600V AC
Accuracy : ±5% of scale length
General
Safety Standard : IEC 61010-1 CAT.III 600V Pollution Degree 2
IEC 61010-2-031
IEC 61557-1/2/4
IP Rating : IEC 60529-IP54
EMC Standard: IEC 61326-1
Withstand Voltage : 3700V AC for 1 minute
Power Source : R6P (AA) (1.5V) × 6
Dimensions : 106(L) × 160(W) × 72(D)mm
Weight : 560g approx.