CATEGORIES
Kyoritsu KEW 3005A
Kyoritsu 3005a digital insulation/continuity tester
|
KYORITSU 3005A DIGITAL INSULATION/CONTINUITY TESTER
- Bargraph to display insulation resistance.
- Displays the value of external AC voltage along with flashing symbol. - Auto null function to automatically subtract the test lead resistance before displaying the real continuity resistance value.
- Live circuit warning beeper.
- Releasing the test button automatically discharges the charges stored in the circuit under test.
- 200mA continuity measuring current to IEC 61557.
- Minimum 1mA current on insulation tests to IEC 61557
Insulation Resistance
Test Voltage : 250V/500V/1000V
Measuring Ranges (Mid-scale Value) : 20MOhms/200MOhms/2000MOhms
Output Voltage on open circuit : Rated test voltage+20%, -0%
Nominal Current : 1mA DC min.
Output Short Circuit Current : 1.5 mA DC approx.
Accuracy :
±1.5%rdg±5dgt (20Mohms/200Mohms)
±10%rdg±3dgt (2000Mohms)
Continuity Test
Measuring Ranges (Mid-scale Value) : 20ohms/200ohms/2000ohms
Output Voltage on open circuit : 7-12V DC
Measuring Current : 200mA DC min.
Accuracy :
±1.5%rdg±5dgt (20ohms)
|±1.5%rdg±3dgt (200?/2000ohms)
AC Voltage
AC Voltage range : 0-600V AC
Accuracy :±5%rdg±3dgt
General Safety Standard :
IEC 61010-1 CAT.III 300V Pollution Degree 2
IEC 61010-2-031 IEC 61557-1/2/4
IP Rating : IEC 60529-IP54
EMC Standard :IEC 61326-1
Withstand Voltage : 3700V AC for 1 minute
Power Source : R6P (AA) (1.5V) × 8
Dimensions :185(L) × 167(W) × 89(D)mm
Weight : 970g approx