AMPROBE 5XP-A
COMPACT DMM WITH NON-CONTACT VOLTAGE
The Amprobe 5XP-A Digital Multimeter provides superior features and accuracy in a smaller form factor. The 5XP-A has unique features such as VolTectT non-contact voltage detection and our exclusive Magne-GripT holster that frees both hands for work. The 5XP-A is the perfect choice for residential, commercial and general troubleshooting applications.
. 27 ranges/10 functions
. Battery load test with 1.5 V and 9 V capabilities
. Data Hold
. Min/Max record minimum and maximum values
. VolTectT non-contact voltage (NVC) detection
. Low battery indication
. Safety rated CAT II 600 V, CAT III 300 V
FEATURES:
DC Voltage 200.0 mV, 2.000 V, 20.00 V, 200.0 V, 600 V
AC Voltage 200.0 mV, 2.000 V, 20.00 V, 200.0 V, 600 V
Current AC/DC 200.0 µA, 2.000 mA, 20.00 mA, 200.0 mA
Resistance 200.0 ohm, 2.000 kohm,
20.00 kohm, 200.0 kohm,
2.000 Mohm, 20.00 Mohm
Continuity beeper
VolTectT Non-Contact Voltage Detection 70 VAC - 600 VAC (50 Hz - 60 Hz)
Capacitance -
Frequency -
Temperature -
Logic test -
Battery test 1.5 V, 9 V
SPECEFICATIONS:
DC Volts ranges: 200 mV, 2 V, 20 V, 200 V, 600 V, Accuracy: ± (1.0 % rdg + 1 dgt)
AC Volts (45 Hz to 500 Hz) ranges: 200 mV, 2 V, 20 V, 200 V, 600 V, Accuracy: ± (1.5 % rdg + 5 dgts)
Voltage resolution: 100 µV
Voltage input impedance: 10 Mohm
Overload protection: 200 mV: 600 V dc or 600 V ac rms (3 minutes) All other ranges: 600 V dc or 600 V ac rms
DC Current ranges: 200 µA, 2 mA, 20 mA, 200 mA, Accuracy: ± (1.5 % rdg + 1 dgt)
AC Current (45 Hz to 500 Hz) ranges: 200 µA, 2 mA, 20 mA, 200 mA, Accuracy: ± (2.0 % rdg + 5 dgts)
Current resolution: 0.1 µA
Input protection: 315 mA/1000 V fast blow ceramic fuse 6.3 mm x 32 mm on mA input
Burden voltage: 300 mV max. (1 V max. on 200 mA range)
Resistance: 200 ohm , 2 kohm , 20 kohm , 200 kohm
Accuracy: ± (1.0 % rdg + 4 dgts)
Resistance: 2 Mohm
Accuracy: ± (1.5 % rdg + 4 dgts)
Resistance: 20 Mohm
Accuracy: ± (2.0 % rdg + 5 dgts)
Resistance resolution: 100 mohm
Open circuit voltage: 0.3 V dc typical, (3.0 V dc on 200 ohm range)
Overload protection: 600 V dc or 600 V ac rms
Continuity: audible indication: 75 ? ± 25 ?, Response Time: 100 ms
Diode test current: 1.0 mA (approximate) ±(1.5 % rdg + 3 dgts)
Diode test resolution: 1 mV
Open circuit voltage: 3.0 V dc typical
Non-ontact voltage indicator: Sense voltage 70 V to 600 V ac; beeper chirps and bright red LED on, works on all ranges
Battery test: 1.5 V, 9 V Accuracy: ± (3.5 % rdg + 2 dgts)